Matching rule reminder
Smallest class with running ≥ continuous AND peak ≥ surge.
Details
Outdoor only · CO risk · never backfeed house wiring.
Reference
Worked running/surge examples and class checks for common US portable inverter screens.
Smallest class with running ≥ continuous AND peak ≥ surge.
Outdoor only · CO risk · never backfeed house wiring.
800 ≤ 1800 and 1200 ≤ 2900 → 1800 class.
Enter running_w 800, surge_w 1200.
Fails 1800/2900 peak; clears 3200/4200 → 3200 class.
Enter running_w 2000, surge_w 3500.
Fails 3200/4200; clears 6800/10000 → 6800 class.
Third class uses verified 6.8/10 kW inverter.
8000 > 6800 running ceiling → NO_MATCH.
Do not force a 6.8 kW class for this continuous load.